- 54 -
(8) If more than 2 generators (No.3, No.4) are
required, apply the same ⑤⑥⑦ procedures.
(9) Turn on the breakers on the load side. If each AC
ammeters show an imbalance in loading, make it in
equal loading by adjusting the speed regulator for engine
rpm. The set is to undertake more load sharing when
the engine rpm. is adjusted higher, while less sharing
when adjusted lower.
[Note]
AC ammeter indicates the current including a cross
current. Wattmeter (Option) is required to know the
correct load sharing.