Loading...
- 85 -
Defect content
Defect
code
Open circuit
error
Machine condition
System responce
(Rail Press. Very Low)
CA2249
Engine stop
IMV
(IMV Solenoid Error)
CA2311
Engine stop
(INJ. Drive Circuit Error)
CA351
Engine stop
#1(L/B #1)
(Injector #1 Open/Short)
CA322
Engine stop
#2(L/B #2)
(Injector #2 Open/Short)
CA331
#3(L/B #3)
(Injector #3 Open/Short)
CA324
#4(L/B #4)
(Injector #4 Open/Short)
CA332
#5(L/B #5)
(Injector #5 Open/Short)
CA323
#6(L/B #6)
(Injector #6 Open/Short)
CA325
(Sensor Sup.1 Volt. Low)
CA352
Drive normally
with bad engine
efficiency
(Sensor Sup.1 Volt. High)
CA386
(Sensor Sup.2 Volt. Low)
CA187
(Sensor Sup.2 Volt. High)
CA227
Ne
(NE Speed Sensor Sup. Volt Error)
CA238
Defect of speed
regulation
(Throttle Sensor Sup. Volt. High)
CA2185
Drive normally
(Throttle Sensor Sup. Volt. Low)
CA2186
(Charge Air Temp. Sensor High)
CA153
Bad cold
performance
(Charge Air Temp. Sensor Low)
CA154
(Ambient Air Press Sensor High)
CA221
Out-put power
reduction
(Ambient Air Press Sensor Low)
CA222
(Water in Fuel)
CA418
Normal drive
(Water in Fuel Sensor High)
CA428
Normal drive
(Water in Fuel Sensor Low)
CA429
(Heater Relay Volt. High)
CA2556
Bad cold-start
performance
Normal drive
(incapable of
driving a glid
heater relay)
(Heater Relay Volt. Low)
CA2555