ELECTROVAP® ELMC
27
30005
Have
4
00000004
maintenance counter
(Hours)
30006
Have
5
00000005
time
(Hours)
30007
Have
6
00000006
time before end-of-season
draining
(Hours)
30008
Have
7
00000007
Control Signal value
10 x V or 10 x mA gold %
30009
Have
8
00000008
Temperature (maintenance
option or SB)
(C)
30010
Have
9
00000009
Error code
0: Normal operating 1: P1 Error 2: P2 Error 3: P3 Error
4: P4 Error 5: P5 Error 6: P6 Error 7: P7 Error 8: P8
Error 9: P9 Error 10: First inspect. 11: Overdue
service
30011
Have
10
0000000A
type of water
1: Tap water 2: Softened water3: Partial DI water 4:
DI water
30012
Have
11
00000000B
type of control
20:On/Off 21: Digital Ctrl 22: Digital Sensor 23: 0-10V
CTRL 24:0-5V CTRL 25:0-20mA CTRL 26:0-10V Sensor
27:0-5V Sensor28:4-20mA Sensor 29: Temp Sensor
30014
Have
13
00000000D
Application
(%)
30015
Have
14
0000000E
steam production
10 x (Kg/hr)
40004
Av
3
00800003
End-of-season (EOS)
(hours) mini - 1 and maxi - 168
40005
Av
4
00800004
Steam capacity limit
(%) mini - 20% and maxi - 100%
40006
Av
5
00800005
rH or demand value (digital or
digital probe).
( %) mini - 1 and maxi - 100
40007
Av
6
00800006
RH set point
( % ) mini - 1 and maxi - 100SB: (C) 25 to 55
40008
Av
7
00800007
Not used)
Not used
40009
Av
8
00800008
Not used
Not used
40010
Av
9
00800009
maintenance interval
(hours / 100) mini - 1 and maxi - 200
40011
Av
10
0080000A
production adjustment
Draining - 1 or evaporation - 2
40012
Av
11
0080000B
anti-foam drain time
mini - 0 sec and maxi 15 sec