ELECTROVAP® ELMC
51
6.4 WATER INLET VALVE
Maintenance of the water inlet valve is to be done after the first 50
hours of operation. Thereafter, twice a year (minimum).
• Switch the appliance off.
• Switch off the water supply to the humidifier and unscrew the
water supply hose.
• Disconnect the power cables from the water inlet valve of your
humidifier (Item 1).
• Loosen the clamp and remove the water supply hose. (Item 2)
• Unscrew the two screws securing the valve (Item 3).
• Pull out your valve, remove the filter with pliers and remove the
coil (Item 4) by prying it off with a screwdriver.
• Run water through the valve body and over the filter to remove
any particles.
Once all these operations completed, please reassemble the unit, taking care to check the condition of the water
supply hose clamp. You can put your appliance back into service.
Ensure that all the clamps are properly tightened whenever the humidifier is maintained.