ELECTROVAP® ELMC
44
5.5 DEFAULT MESSAGE
Meaning:
The signal passing through the contactor is OFF when it should be ON. The contactor no longer works and there is no
steam production.
In this case:
When this message appears, the cylinder is drained, the general fault contact is activated, and the unit is then stopped.
Causes and remedies:
1. Check the F1 (2A) fuse on the main map.
2. Check the connection of the connector wires of the contactor
3. Make sure the X01 (wire 12 and 13) is well connected to the map
4. Change the faulty contactor
Meaning:
The signal passing through the contactor is ON when it should be OFF. The contactor has a defect and produces steam
when it should not.
CAUTION : switch the humidifier off before any handling
In this case:
When this message appears, the cylinder is drained, the general fault contact is activated, and the unit is then stopped.
Causes and remedies:
1. Turn off the device
2. Check the condition of the contactors visually
3. Make sure the X01 (wire 12 and 13) is well connected to the map
4. Change the faulty contactor
Meaning:
The water inlet valve is defective, the high level is not reached after 20 minutes.
In this case:
When this message appears, the cylinder is drained, the general fault contact is activated, and the device is not
stopped.
Causes and remedies:
1. Make sure the water supply faucet is open
2. Check for water in the cylinder
3. Change the water inlet valve