5.4 MAINTENANCE ALERTS
After 10,000 hours of operation, it is recommended to
replace the contactor. The unit is not stopped
M3: MAINTENANCE
NOT DONE: PURGE
This message appears if 100 hours elapsed between the
appearance of the M2 and M3 message and no
maintenance has been done.
Then the unit is shut down and follows the procedure:
1. 1. Emptying the cylinder
2. 2. Cooling the cylinder
3. 3. Ready for maintenance
The maintenance timer has arrived at 0, it is necessary to
do the maintenance of the device. The unit is not stopped
This message will appear 50 Hrs after the first start.
It is then necessary to check the correct tightening of
electrical and hydraulic connections (steam pipe, drain
system, water supply...). The unit is not stopped
TO CARRY OUT A RESET FOR THE ABOVE
MESSAGES, FOLLOW THIS PROCEDURE:
-Switch the unit to drain by pressing the manual drain button (4).
-Press button 3 for at least 5 seconds.