ELECTROVAP® ELMC
21
3.7 ELECTRICAL CONNECTIONS
All work on the electrical parts must be carried out by qualified and authorized personnel.
In addition, before making any electrical connections, check that your installation has been determined
from the values in the below table.
Respect local regulation concerning electrical connections.
Electronic components are sensitive to electrostatic charges. When working on these components, take
appropriate measures to avoid electrostatic discharges.
3.7.1 Technical data
Single-phase
200-230V
Three-phase
200-230V
Three-phase
380-420V
Three-phase
440-480V
Three-phase
575-600V
Three-phase
690V
Maximum
steam prod.
[Kg/h]
Maximum amperage for installation [A]
5
18
12
6.5
6
4.5
4
7
17
-
-
-
-
8
-
-
10
9
7
6
9
21.5
-
-
-
-
10
35
-
12.5
11
8.5
7.5
13
30.5
-
-
-
-
15
-
-
18.5
16.5
12.5
10.5
17
40.5
-
-
-
-
20
-
-
24.5
21.5
16.5
14
27
-
63
-
-
-
-
30
-
-
36.5
32
25
20.5
33
-
-
40
35
27
22.5
35
-
80.5
-
-
-
-
40
-
-
48.5
42.5
33
27.5
43
100
-
-
-
-
50
-
60.5
53
41
34
52
-
120.5
-
-
-
-
60
-
73
63.5
49
41
66
-
-
78
69
53
45
90
-
109
95
73
61
99
-
-
116
103.5
80.5
67