ELECTROVAP® ELMC
41
CONTROL SIGNAL IN
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXX
XXXXX
MENU: CHANGING
UNIT CONFIGURATION
STEAM CAPACITY
LIMIT XX%
Any press on enter key
from any of these menus
MENU: HUMIDIFIER
STATUS
VALUE: 1 step (ON/OFF) / CTRL or Digital Probe / 0-10V,
4-20mA, 1-5V controller / 0-10V, 0-5V humidity sensor
VALUE: If ON/OFF control between 20 and 100 %,
Otherwise between 50-100 %
ADJUST SET POINT
XX%HR
ADJUST PROP BAND
XX%
MAINTENANCE FRE-
QCY XXXXXKG
MAINTENANCE
INTERVAL 300H
FOAM / SCALE
CONTROL XX sec
POWER OFF IF
DRAINING: Xxx
VALUE: between 0 and 999000kg or between 0 and
2000h
Adjusts the estimated number of kg of steam or number
of hours of operation before a visual check of the
cylinder. If you need to clean it, please refer to the
maintenance pages of the manual, if not you can then
increase this maintenance frequency.
Set at 300h out of the factory
VALUE: between 0 and 10 seconds
Allows you to set the time for a small drain. If there is
foam inside the cylinder, increase the time. This foam
phenomenon usually appears with softened water
VALUE: YES or NO
Cuts the contactor(s) during a drain and avoids leakage
currents
VALUE: between 10 and 99 %
VALUE: between 1 and 50%
ADJUST STEAM BY:
XXXXXXXXXX
VALUE: EVAPORATION (necessary for demineralized
water) or DRAINING