ELECTROVAP® ELMC
46
Meaning: Draining is not properly done
In this case:
When this message appears, the cylinder is drained, the general fault contact is activated, and the device is stopped.
Causes and remedies:
1. The drain system is clogged. Press the manual drain button, and check for the proper flow of water. Then clean
the inside of the cylinder. Check if there is limestone in the valve.
Alarm
P8
Information "CLEAN CYLINDER + DRAIN VALVE"
TO CARRY OUT A RESET FOR THE ABOVE
MESSAGES, FOLLOW THIS PROCEDURE:
-Switch the unit to drain by pressing the manual drain button (4).
-Press button 3 for at least 5 seconds.
5
1
2
3
4