EasyManua.ls Logo

DIG 720A Series - Page 24

DIG 720A Series
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
Example: If program A has valve 1 set at a run time of 0:01 and program B has
valve 1 set at a run time of 0:00, then setting a SimpleSmart
program for valve
1 will not include program B’s valve 1 because it is off. If program B’s valve 1
was intended to be included in the program calculation, then program B’s valve
1 needs to be set to a nonzero run time before setting the SimpleSmart
option.
Changing a run time of the valve while a SimpleSmart
program is active will
turn off the SimpleSmart
program and it will have to be reactivated each time
a run time is manually adjusted.
NOTE: If using one of the SimpleSmart
presets we recommend evaluating the
plants’ health for the first month and making adjustments to the system as needed.
If an adjustment or fine tuning of the SimpleSmart
programming is required, this
adjustment can be made for each month in the Seasonal Adjustment (%) Setting
(see section 9.7).
Example: The user entered watering run time will be adjusted monthly based
upon the forecast ET pattern for the selected region.
By selecting SP02, the controller may adjust the programmed run time of valve 1
from 10 minutes per program, to 3 minutes or less per program. This reduces the
irrigation run time by 7 minutes, providing a water savings of 70% for the month of
January.
9.6.2 TO ACTIVATE THE SIMPLESMART
ET
FEATURE:
1. Press or until you see on the bottom
of the display.
2. Press
and OFF will begin flashing for
valve 1.
3. Press or to select one of the twenty
preset programs (see Chart A on page 21).
4. Press
to confirm your settings.

Related product manuals