IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 30 di 38
CF19 Pb4 input polarity
0= active for closed contact
1= active for open contact
0 1
CF20 RL4 configuration of the relay 4
0= Reversing valve
1= ON / OFF condenser fan
0 1
CF21 RL5 configuration of the relay 5
0= General alarm
1= one compressor with 1 stage valve
2= Compressor 2
3= ON / OFF condenser fan
0 3
CF22 4mA corresponding to the pressure value of the transducer 0.0
0
31.0
449
Bar
Psi
Decimal
integer
CF23 20mA corresponding to the pressure value of the transducer 0.0
0
31.0
449
Bar
Psi
Decimal
integer
CF24 Pb1 Offset -12.0
-21.6
12.0
21.6
°C
°F
Decimal
integer
CF25 Pb2 Offset -12.0
-21.6
12.0
21.6
°C
°F
Decimal
integer
CF26 Pb3 Offset -12.0
-21.6
-12
-174
12.0
21.6
12
174
°C
°F
Bar
Psi
Decimal
Integer
Decimal
integer
CF27 Pb4 Offset -12.0
-21.6
12.0
21.6
°C
°F
Decimal
integer
CF28 Chiller or Heat Pump starting command priority
0= Instrument keyboard
1= Digital Input
2= Analogue input (probe)
0 2
CF29 Automatic Changeover Setpoint -40
-40
110
230
°C
°F
Decimal
integer
CF30 Differential for functioning mode 0.0
0
25.0
45
°C
°F
Decimal
integer
CF31 Chiller or Heat pump key configuration
0=
chiller / heat pump
1=
chiller / heat pump
0 1
CF32 Celsius or Fahrenheit selection
0= °C / °BAR
1= °F / °psi
0 1
CF33 Power supply frequency
0= 50 Hz
1= 60 Hz
0 1
CF34 Serial Address for monitoring 1 247
CF35 Remote terminal keyboard
0= 4 keys
1= 6 keys
2= 6 keys with NTC probe mounted on board
0 2
CF36 Default display read-out
0= Pb1 / probe
1= Pb2 / probe
2 =Pb1 / rtC
3= Pb2 / rtC
0 3
CF37 Firmware Release