CF38 Eeprom – Parameter mapping
Pr2 Password value 0 999
Dynamic Setpoint
Parameter Description Min Max Meas Resolution
Sd01 Dynamic Setpoint
0= Not enabled
1= Enabled
0 1
Sd02 Maximum summer dynamic Offset - 30
-54
30
54
°C
°F
Decimal
integer
Sd03 Maximum winter dynamic Offset - 30
-54
30
54
°C
°F
Decimal
integer
Sd04 External air d. setpoint during summer -40
-40
110
230
°C
°F
Decimal
integer
Sd05 External air d. setpoint during winter -40
-40
110
230
°C
°F
Decimal
integer
Sd06 External air differential during summer - 30
-54
30
54
°C
°F
Decimal
integer
Sd07 External air differential during winter - 30
-54
30
54
°C
°F
Decimal
integer
Pr2 Password value 0 999
Energy Saving
Parameter Description Min Max Meas Resolution
ES01 Energy saving starting hour (0÷24) 0 23.50 Min 10 Min
ES02 Energy saving ending hour (0÷24) 0 23.50 Min 10 Min
ES03…ES09 Monday…Sunday
0 = Not enabled
1= Enabled
0 1
ES10 Energy saving setpoint offset in chiller -30.0
-54
30.0
54
°C
°F
Decimal
integer
ES11 Energy saving differential in chiller 0.1
0
25.0
45
°C
°F
Decimal
integer
ES12 Energy saving setpoint offset in heat pump -30.0
-54
30.0
54
°C
°F
Decimal
integer
ES13 Energy saving differential in heat pump 0.1
0
25.0
45
°C
°F
Decimal
integer
Pr2 Password value 0 999
Compressor parameters
Parameter Description Min Max Meas. Resolution
CO01 Minimum ON time 0 250 Sec 10Sec
CO02 Minimum OFF time 0 250 Sec 10Sec
CO03 ON delay time between two compressors or Comp. and
valve
1 250 Sec
CO04 OFF delay time between two compressors or Comp. and
valve
0 250 Sec
CO05 Output time delay after power supply start-up 0 250 Min
CO06 Compressor On delay time after Pump/”Supply fan”
activation
1 250 Sec
CO07 Compressor OFF delay time after Pump/”Supply fan” de-
activation
0 250 Sec
CO08 Compressor rotating control
0= Enabled
1= Fixed sequence
0
1
CO09 Nod Used