IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 32 di 38
CO10 Stage vale polarity
0= Capacity stage ON
1= Capacity stage OFF
0 1
CO11 Pump/”Supply fan” operating mode
0= Not used
1= Continuously
2= Only for compressor demand
0 2
CO12 Compressor 1
0 = Enabled
1 = OFF
0 1
CO13 Compressor 2 / Stage valve.
0 = Enabled
1= OFF
0 1
CO14 Hour counter setpoint for 1
st
compressor 0 999 Hr 10 Hr
CO15 Hour counter setpoint for 2
nd
compressor 0 999 Hr 10 Hr
CO16 Hour counter setpoint for pump/”Supply fan” 0 999 Hr 10 Hr
Pr2 Password 0 999
Fan control parameter
Parameter Description Min Max Meas. Resolution
FA01 Fan output
0= Enabled
1= Not enabled
0 1
FA02 Fan regulation
0= On when compressor On
1= ON / OFF
2= Proportional speed control
0 2
FA03 Fan related to compressor
0= With compressor
1= Independent from compressor
0 1
FA04 Maximum speed time when the fan starting 0 250 Sec
FA05 Phase difference fan 0 20 Micro
Sec
250µs
FA06 Not used
FA07 Cooling pre-ventilation before ON compressor 0 250 Sec
FA08 Minimum fan speed in summer 30 100 %
FA09 Maximum fan speed in summer 30 100 %
FA10 Temperature / pressure setpoint for minimum speed in
summer
-40.0
- 40
0.0
0
110
230
30
435
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA11 Temperature / pressure setpoint for maximum speed in
summer
-40.0
- 40
0.0
0
110
230
30
435
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
FA12 Proportional band in summer 0.0
0
0.0
0
25.0
45
30.0
435
°C
°F
Bar
Psi
Decimal
integer
Decimal
Integer