EasyManua.ls Logo

DMP Electronics XTLplus SERIES - Bell Options

DMP Electronics XTLplus SERIES
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital Monitoring Products XTLplus Installation and Programming Guide
26
BELL OPTIONS
Bell Options
29.1 Bell Options
This section allows you to program the panel bell output functions. If using the
Model 1135 or 1135DB Wireless Siren, the Trip with Panel Bell option should be
selected in the Output Information programming for the siren.
29.2 Bell Cuto Time
Enter the maximum time from 1 to 15 minutes that a wireless output remains on. If
the output is manually silenced or the system is disarmed, the cuto time is reset.
Default is 5.
29.3 Automatic Bell Test
When YES is selected, the 1135/1135DB wireless siren is turned on for two seconds
when all areas in the system are armed. The Bell Test only occurs when the areas
are armed from a keypad. Arming performed from an Arming zone or remotely
from Remote Link™ does not activate the Bell Test.
Closing Wait operation
When Bell Test is set to YES, the closing wait function also operates. Closing Wait
provides a delay time before a monitored system arms until the panel receives an
acknowledgment of the closing report from the central station receiver. During the
delay, the keypad displays ONE MOMENT . . . Once the closing is acknowledged,
the keypad buzzes for one second and then displays the ALL SYSTEM ON message. If
communication fails, the message LOCAL ALARM ONLY appears.
29.4 Bell Output
Enter the output number (51-54, 61-64) for an 1116 or 1117 wireless output
when needed to follow the on and o condition of the bell action. Enter 0
(zero) to disable.
Note: When BELL ACTION below is set to T for Temporal Code 3, this Bell Output
action will be Pulse for wireless outputs 51-54 and 61-64.
29.5 Bell Action
This denes the type of Bell Action from zone alarms that will occur. Trouble
conditions do not activate Bell Action. There are seven zone types you can
program individually for Bell Output. To provide a steady Bell Output, enter S.
For a pulsed output, enter P. For a Temporal Code 3 output, enter T and for no
bell action, enter N.
29.5.1 Fire
Denes Bell Action for Fire Type Zones. The default is set at T.
29.5.2 Burglary
Denes Bell Action for Burglary Type Zones. The default is set at S.
29.5.3 Supervisory
Denes Bell Action for Supervisory Type Zones. The default is set at N.
29.5.4 Panic
Denes Bell Action for Panic Type Zones. The default is set at N.
29.5.5 Emergency
Denes Bell Action for Emergency Type Zones. The default is set at N.
29.5.6 Auxiliary 1
Denes Bell Action for Auxiliary 1 Type Zones. The default is set at N.
29.5.7 Auxiliary 2
Denes Bell Action for Auxiliary 2 Type Zones. The default is set at N.
BELLOPTIONS
BELLCUTOFF: 5
BELLTEST NO YES
BELLOUTPUT: 0
BELLACTION...
FIRE TYPE: T
BURGLARYTYPE: S
SUPRVSRYTYPE: N
PANIC TYPE: N
EMERGNCYTYPE: N
AUXLRY1 TYPE: N
AUXLRY2 TYPE: N

Table of Contents