XTLplus Installation and Programming Guide Digital Monitoring Products
47
COMPLIANCE
Household Burglar-Alarm System Units
ANSI/UL 1023
38.1 Bell Cuto
The bell cuto time cannot be less than 4 minutes.
38.2 Entry Delay
The maximum entry delay used must not be more than 45 seconds.
38.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
38.4 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1106 transmitters must be programmed Normally Closed.
38.5 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero).
38.6 Wireless Audible Annunciation
The Wireless Audible option must be selected as DAY for residential applications.
38.7 Panel location
Mount panel inside protected area.
38.8 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
Central Station Burglar Alarm Units
ANSI/UL 1610
39.1 Supervision
Commercial Burglary is provided when the Check-in and Fail Time time is set to 3 minutes.
39.2 Remote Disarm
REMOTE DISARM must be programmed as NO.
39.3 Central Station
MESSAGE TO TRANSMIT programming for zones must not be set to LOCAL (L).
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
40.1 Bell Output Denition
The bell output of the Model XTLplus must be programmed to operate steady on burglary alarms and
temporal on re alarms.
40.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
40.3 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for re devices.
40.4 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication
(FV) zone type.
40.5 Battery Standby
For listed applications, the panel must have 24 Hour battery standby operation. The Model XTL+BAT3500
battery should be used for re installations.
40.6 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.