58
ED50/ED100/ED250 09-2021DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Mode switch type

 - 
Internal, operator mounted mode switch is active.
External mechanical mode switch with contacts is connected to operator terminal
board.
Internal mode switch connector must be removed.
External DCW electronic mode switch (EPS) is connected to operator terminal
board. Internal mode switch connector must be removed.
Mode switch control by TMS Soft control software.
DCW Mode switch (EPS) is installed, and operator is also connected by the
building management system to TMS Soft control software.
When PS is set to , the Mode switch functions can be changed from
DCW (EPS) to TMS Soft..
DCW® Electronic mode switch (EPS)
behavior following power reset

 - 
In event of power failure, or if operator is deliberately switched off, EPS will
automatically switch to last known position when power returns.
Important: The time at which power returns might not be during business
hours and may affect insurance-compliant door locking requirements.
In event of power failure, or if operator is deliberately switched off, EPS will
automatically switched to OFF position when power returns.
This function should be used iif insurance compliant locking if required.
Internal program switches, switch on delay

 - 
Operator will perform function of new switch setting as soon as internal program
switch is moved.
Operator will perform function of new switch setting after a delay of
 seconds from when internal program switch is moved.
This function is useful if user has to pass through door and its connected
detectors and sensors after program switch is set to new function.
Unlocking during business hours

 - 
Door is always locked when it reaches closed position.
In automatic mode, door will not lock when it reaches closed position. This
achieves faster door opening when system is equipped with motor driven locks.
If an electric strike opener is used, it must be suitable for % continuous
duty factor to avoid possibility of damage.
A.. Driving parameters detail.