60
ED50/ED100/ED250 09-2021DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Factory setting level
Parameter SL is used to determine what data will be reset during factory setting
process.
Reset Standard factory settings (SL= default)
. Mode switch: CLOSE.
. Door closed.
. Press  button keypad down button
for greater than  s.
All parameters reset to factory settings.
Procedure completed when "" on  digit displays blinks twice.
Installed upgrade cards remain valid and do not require reinstallation.
. Learning cycle required.
 Reset Extended factory settings (SL=)
. Mode switch: CLOSE.
. Door closed.
. Set SL to .
. Press  button keypad down button for greater than  s.
All parameters reset to factory settings.
Installed upgrade cards deleted from operator memory.
Parameter SL automatically reset to .
Control unit and upgrade cards can be used independently (delivery status).
Procedure completed when "" on  digit displays blinks twice.
. Learning cycle required..

1 - 2
Opening angle
Door opening angle set during learning cycle is displayed.
Opening angle can only be changed during learning cycle.
Due to installation and parameter tolerances, display value may not match actual
door position.

- 
°
Door closer mode

 - 
=Automatic mode. This mode is applicable whenever door is mainly opened
automatically and where motion detectors are installed.
Mode is optimized for high frequency use.
Full energy upgrade card provides for higher door opening and closing speeds.
In case door is blocked during a closing cycle, operator reverses automatically.
Driving phase is optimized to provide reliable closing cycles.
Keep closed force (wind load control) parameter FH and Push & Go function
parameter PG are only available in automatic mode.
=Manual mode. This mode is applicable whenever door is mainly used manually
and only rarely automatically.
In case door is blocked during a closing cycle, door will stop at its current
position.
Driving phase optimized for manual opening cycles.
Power assist function parameter hf is only available in manual mode.
Power assist activation angle
Setting of door activation angle for Power assist function (hF).
Higher settings of hA result in better spring force compensation for easier manual
opening.
Power assist function is more sensitive the smaller the activation angle.

 -  °
A.. Driving parameters detail.