62
ED50/ED100/ED250 09-2021DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Upgrade card barrier-free toilet
. Once upgrade card installed, parameter value will automatically change to
(upgrade card installed, function not activated).
. Activate function by changing parameter F to .
. Operator power reset is required; turn power switch off, wait s and turn power
back on.
• Upgrade card assigns inputs and outputs of the control unit with functions which are
required for this application.
Available
upgrade card
codes
(Para. A..)
, ,
,
Upgrade card DCW
. Activate function by installing upgrade card, parameter value will automatically
change to .
• Upgrade card provides operator with DCW bus connection.
• Plug for terminal board X socket included with upgrade card.
• DCW bus enables connection of:
• Program switch EPS DCW (max. )
• Motor lock controls SVP-S x DCW (max. )
• Motor lock SVP (max. )
• RM-ED lintel mounted smoke detector
• Key switch button ST DCW (max. )
• I/O module DCW (max. )
Available
upgrade card
codes
(Para. A..)
, ,
COM configuration interface
0 - 1
Interface programmed for communication with dormakaba handheld.
Interface programmed for use with dormakaba TMS Soft control software.
Backcheck when door opened manually
• Angle after which door is braked when manually opened.
• Back check level is automatically optimized during manual door opening cycles.
• bc function improves door braking behavior in end position so door does not move
beyond set opening angle OA
. Entered bc value is subtracted from set opening angle OA, example:
• Opening angle, °:
Parameter bc, °, door back check starts at °.
-
(v.)
°
Door thickness
. Enter parameter Td in mm.
• Door thickness affects measured door opening angle.
• Parameter Td enables a more accurate door width to be entered, if required.
- mm
Td
-
/"
/"
Deactivation of drive; X, and a, trigger
type
0 - 1
NC contact, drive function is deactivated when NC contact is open.
NO contact, drive function is deactivated when NO contact is closed.
Night-bank contact X; and , trigger
type
0 - 1
. NO contact, night-bank function is triggered when NO contact is closed.
• Typically used when using a key switch or an access control system.
. NC contact, night-bank function is triggered when NC contact is opened.
• Typically used when connected to building management system to trigger
doors (signal normally present).
A.. Driving parameters detail.