EasyManua.ls Logo

Dover ProGauge MagLink LX Plus - Page 68

Dover ProGauge MagLink LX Plus
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Maximum Wiring Length*: 305 m (1,000 ft.) field wiring
Alarm Threshold Configuration: Fully Automatic
Diagnostic Reading on sensor setup:
0 to 0.5 (normal),
485 to 495 (in alarm)
Multi-Drop Restriction
Maximum points per channel = 12 points,
924B and DMP Probes = 4 points,
ISIM Smart Sensors = 1 point
Devices can be mixed in any combination to hold a maximum of 12
points on one channel
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *This is the maximum length of wire to be used to connect all sensors on one channel.
This length includes the wire from the Barrier to each sensor board in the string.
Installation
WARNING: Make sure you read and fully understand the warnings and
information found in the Hazardous Areas section of your console's
Installation Guide before you install or do the servicing of this sensor.
CAUTION: ALWAYS obey Local and National Electrical Codes applicable to
the installation location.
Make sure that the cables (gas and oil resistant OPW Fuel Management
Systems part # 12-1030) from the field wiring to the controller are in conduit
that is dedicated to intrinsically safe wiring.
Use wire-nuts and epoxy-resin seal-packs for field connections (refer to M00-
390008 Waterproof Electrical Connections for information).
NOTE: If this sensor is used to monitor a normally dry well, use a meter to set the float position
so the sensor is in a closed position when there is NO liquid level (the float will be in the lower
position). To monitor a normally wet well, use a meter to set the float so that the sensor is in a
closed condition WITH a liquid level (the float will be in the upper position).
l This sensor uses ONE Controller Interface I.S. Module position
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 68

Table of Contents

Other manuals for Dover ProGauge MagLink LX Plus

Related product manuals