l Start with the Connections table and “Typical Installation" drawing below.
l Make sure the sump pit or pan is dry.
l Install the sensor on the bottom of the sump/pan. Attach the sensor wire to a pipe or bracket with a tie
wrap.
l Connect the sensor cable to the sensor.
l Connect the sensor wires to the field wires in the junction box. Use the supplied cable gland and silicon
wire nuts.
l Seal the electrical connections with the epoxy seal packs (refer to M00-390008 Waterproof Electrical
Connections for instructions).
l Install explosion-resistant sealing fittings at both ends of the conduit. Refer to the Probe-Cable Seal-
offs section of the console's Installation Guide for instructions.
Connections
Sensor Wire Color 12V Smart Sensor Interface Channel
Red Power
Black (hydrocarbon sensor) Signal
Shield (or 3rd conductor) Ground
Typical Installation Drawing
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 69