Controller Setup
The sensor must be Auto Detected on the console. Refer to the M2051 MagLink LX4/LX Plus Cofiguration
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection.
Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
Float Sensor Test
CAUTION: Use caution to prevent dangerous conditions when you do work in
a hazardous area.
Make sure that the area has sufficient airflow when you do a test or remove
contamination from the sensor. Make sure there are no open flames or hot
surfaces near the work area.
l Turn the sensor so the bottom opening points up and wait for a minimum of two (2) minutes.
l Make sure that the controller is not in an alarm condition.
l Put the sensor back in its normal position. Make sure that the alarm condition stops.
If the controller does not go into an alarm condition, look to see if the thresholds are correctly programmed in
the system. Look to see if the float is in the correct position (refer to the applicable instruction above). A
sensor or wiring fault will cause a system alarm. Do a continuity test in the wiring and junction boxes. Make
sure there is continuity with no short circuits.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 70