[331] Module Events 1
1/2 Module AC Trouble/Restore
This reporting code is transmitted when a module’s AC supply fails or has been restored. A programmable delay applies to
both the trouble and the restore. This reporting code is sent to the System Maintenance call direction group.
3/4 Module Battery Trouble/Restore
These reporting codes are transmitted when a module’s battery voltage falls below 11.5VDC or is restored. These reporting
codes are sent to the System Maintenance call direction group.
5/6 Module Battery Absent/Restore
These reporting codes are transmitted when a module’s battery is detected as absent or restored. These reporting codes are
sent to the System Maintenance call direction group.
[332] Module Events 2
1/2 Module Low Voltage Trouble/Restore
Sent when module voltage drops below acceptable levels or is restored.
3/4 Module Supervisory Trouble/Restore
Sent when communication with a module is lost or restored.
5/6 Module Aux Trouble/Restore
Sent when a high current output module or power supply module experiences an auxiliary voltage supply trouble.
[335] Module Events 5
1/2 Output 1 Fault/Restore
This reporting code is sent when the first output on the high-current output expander module goes into fault (open or short)
or is restored.
Only the first output on the high-current expander module is supervised.
[351] Alternate Communicator 1
1/2 Alt. Comm Communications Fault/Restore
Sent when the system loses or restores communications with the alternate communicator.
3/4 Not used
5/6 Not used
7/8 Alt. Comm Radio/SIM Failure/Restore
Sent when the alternate communicator experiences trouble or restore of the radio/SIM.
[352] Alternate Communicator 2
1/2 Alt. Comm Network Fault/Restore
Sent when the alternate communicator loses or restores communication with the network.
5/6 Alt. Comm Ethernet Trouble /Restore
Sent when the alternate communicator detects a network absent condition or DHCP failure or restore.
[354] Alternate Communicator 4
Receiver 1 to 4 Trouble and Restore
Sent when the alternate communicator detects a trouble or restore condition on receiver 1-4.
1/2 Receiver 1 Trouble/Restore
3/4 Receiver 2 Trouble/Restore
5/6 Receiver 3 Trouble/Restore
7/8 Receiver 4 Trouble/Restore
[355] Alternate Communicator 5
Receiver 1 to 4 Supervision Failure and Restore
Sent when the alternate communicator detects a supervision trouble for the Ethernet receiver (1, 2) or the GPRS receiver (3,
4).
1/2 Receiver 1 Supervision Failure/Restore
3/4 Receiver 2 Supervision Failure/Restore
5/6 Receiver 3 Supervision Failure/Restore
- 105 -

Table of Contents

Other manuals for DSC HS2016

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC HS2016 and is the answer not in the manual?

DSC HS2016 Specifications

General IconGeneral
Mounting TypeWall mount
Power Supply16.5VAC
Battery Backup12VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Dimensions267mm

Related product manuals