EasyManua.ls Logo

DSE DSE892 SNMP - MODBUS

DSE DSE892 SNMP
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setup
35
6.4 MODBUS
NOTE: This section is only used when setting up the DSEGateway
®
to operate as a
communications protocol convertor. This section should be left with no entries if using the
DSEGateway
®
purely as an SNMP or email notification system.
This page is used to configure the DSEGateway
®
as a Modbus Gateway to allow conversion across
the various ports.
It can be used for example to set USB as a modbus master to connect to any DSE controller fitted
with a USB port and supporting the DSE Configuration Suite SCADA function.
SLAVE (Settings of the DSEGateway
®
port this is connected to the monitoring device)
Parameter
Description
ID Modbus slave address of the selected DSEGateway
®
port
Port The incoming port of the DSEGateway
®
RS232
RS485
Ethernet
USB
TCP Port/Serial
Baud
When
Port
is set to
Ethernet
TCP port to use for Modbus (usually 502)
When Port is set to RS232/RS485 – Baud rate of the selected port.
MASTER (Settings of the DSEGateway
®
port that is used to connect to the DSE controller)
Parameter
Description
ID Modbus slave address of the connected DSE controller
Port The outgoing port of the DSEGateway
®
RS232
RS485
Ethernet
USB
TCP Port/Serial
Baud
When
Port
is set to
Ethernet
TCP port to use for Modbus (usually 502)
When Port is set to RS232/RS485 – Baud rate of the selected controller.

Related product manuals