27
NO
NO
YES
FIGURE 6-3 - Low Water Cutoī§ - Detail
6.6 External Optional Low Water Cut Oī§
These guidelines are supplied when necessary to install an
īīīīīīīīīīīīÆīīīīŗīīīīīī¦īīīī²ī§īīīÆīŗī¦ī²īīīīīīīīīīīīīīīīīīīīīīīīīīī
īīīīīīīīīīīīīīīīīīīīīī
īīīīīīīīīīīīīīīīīīīī
īīīīīīī¤īīīīīīīīīī«īīīīīī
Jurisdiction.
Follow LWCO manufacturer installation instructions for type of
LWCO selected in addition to these instructions.
LWCO shall be 120V/60HZ control and dry contacts sized for
load being connected. Wire control to boiler. See Figure 6-4.
Connect LWCO device to the system ground. Ground in
īīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīī
īīīīīīīīīīīīīīīīīīīīīīīīīī
īīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīīī
National Electrical Code (NEC) or Canadian Electrical Code
CEC.
⢠Locate LWCO sensing device in the supply
piping, above the minimum height of boiler.
See Figure 6-2, Piping Diagram.
⢠Position control in HORIZONTAL piping to assure proper
boiler protection (upright or 90° rotation).
⢠For proper operation, sensing element of the LWCO
control shall be positioned in the tee to sense the main
īīīīīīīīīīīīīīīī°īīīīīīīīīīīīīīīīīīīī“īīīīīīīīīīīīīīīīīīī
walls. Element shall NOT contact the rear, or side walls of
the tee. See Figure 6-3.
⢠Install an air vent using a tee to avoid nuisance
shutdowns.
⢠Apply small amount of pipe sealant to threaded
connections.
⢠Arrange piping to prevent water dripping onto boiler.
⢠ī§ī²īī±ī²ī·īīīīīīīīīīīīīīīīīīīīī§īīīīīīīī
īīīīīīīī
īīīīīīīīīī
LWCO sensing device.
īÆīīīīŗīīīīīī¦īīīī§īīīÆīŗī¦ī²ī
Electrical Conduit
J-Box
120 V/60 HZ
Conduit or Power
Supply cord
(Polarized)
L
1
N
G
GND
L
1
N
GND
BLK
WHT
120 V/60 HZ Socket
(Polarized) 120 V/60 HZ
Cord Set From Boiler
N.O
FIGURE 6-4 - LWCO Wiring Diagram
6 - HYDRONIC PIPING
240012564 REV A, [05/15/2019]