Dunkirk DCBF-125 - 2 Introduction

Dunkirk DCBF-125
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
Check our website frequently for updates: www.ecrinternational.com
Information and specications outlined in this manual in eect at the
time of printing of this manual. ECR International reserves the right to
discontinue, change specications or system design at any time without
notice and without incurring any obligation, whatsoever.
2.5 Designated Use
• DCCF-150 provide both central heating and domestic
hot water.
• DCBF-125 central heating only.
• Indoor installation.
• Closet or alcove installation. Direct Vent Boiler does not

• Direct vent boiler.
• 
(LP/propane).
2.6 The unit MUST NOT:
• Directly heat potable water. Indirect heating is
acceptable.
• Heat water with non-hydronic heating system
chemicals present (example, swimming pool water).
• Toxic chemicals, such as those used for boiler
treatment, shall not be introduced into potable water
used for space heating.
• Exceed 43 psig (2.96 bar) maximum system pressure,
or drop below minimum system pressure 7.25 psig
(.50 bar)
• Exceed 176°F (80°C) system design temperature.
2.7 Operational Features
• Modulates to provide CH Turndown 5.5:1, DHW
Turndown 7:1.
• Maximum output available for domestic hot water:
DCCF-150 - 136,000 btu/h (40 kW), capable of
providing 3.5 (U.S.) gpm (13.2 liters/min) with a
temperature rise of 70°F/39°C.
• 
• Optional Outdoor Temperature Reset.
• Heat exchanger over heat protection.
• Boiler operating at maximum operating temperature,
providing heat, pressure gauge should not indicate
more than 26.11 psi / 1.80 bar. If reading exceeds this

2 - Introduction
2.1 

UNITED STATES
• National Fuel Gas Code, ANSI Z223.1/NFPA 54
.
• National Electrical Code, NFPA 70.
2.2 
installation shall conform to Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.

2.3 Requirements for Commonwealth of
Massachusetts:
Boiler installation must conform to Commonwealth of
Massachusetts code 248 CMR which includes but is not limited
to:

2.4 Manufacturer recommends use of Carbon
Monoxide monitor may be requirement of local
jurisdiction.
2 - INTRODUCTION
240012564 REV A, [05/15/2019]