45
10.1 Testing For Gas Leaks And Purging The Gas
Supply

angles to valve). Pressure test gas supply and inlet pipe
work connection to boiler gas service cock for soundness.
Loosen screw of pressure inlet gas test port on gas valve.
See section 13.4 Gas Valve. Verify gas supply is ON.
Open boiler service cock to purge.
Retighten test port screw and test for gas leaks. Close

WARNING
If you do not follow these instructions exactly,
a re or explosion may result causing property
damage, personal injury or loss of life.

which automatically lights burner. Do NOT try to
light this burner by hand.
Before operating smell all around appliance area for


Use only your hand to turn the gas shuto
valve. Never use tools. If valve will not turn by

technician. Force or attempted repair may result in

Do not use this appliance if any part has been
under water.
technician to inspect appliance and to replace any
part of control system and any gas control which
has been under water.
!
FOR YOUR SAFETY READ BEFORE OPERATING
CAUTION
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.

department.
!
10 - OPERATING INSTRUCTIONS
10.2 Boiler Operation
Domestic hot water supply always takes priority over central
heating.

boiler automatically switches to hot water mode until demand

This interruption in central heating is only when demand for
hot water is present and should not be noticed by the User.
10.3 Central Heating Mode
1.
With demand for heating, pump circulates water through
the primary circuit.
2.
Combustion fan comes on at ignition speed, closing the air
pressure switch, allowing power to spark generator and
gas valve, creating ignition in the combustion chamber.
3.

combustion chamber sending a signal to the control board.
4.
After initial stabilization period the control board monitors
supply and return temperatures and modulates fan speed
and gas rate accordingly.
5.

shutdown and enter 3 minute anti-cycling mode. The
boiler pump will operate for 3 minutes to dissipate any
residual heat.

minutes to operate.
10.4 Domestic Hot Water Mode


Water in the boiler is diverted from central heating system
to domestic hot water heat exchanger to heat incoming
domestic water.
Combustion fan will come on at ignition speed, closing

spark generator and gas valve, creating ignition in the
combustion chamber.

combustion chamber and send a signal to the control
board.
After initial stabilization period, the control board monitors
supply and return temperatures and modulates fan speed
and gas rate accordingly.
Domestic call for heat ends when tap is closed and DHW

There is no anti-cycling mode after a DHW call for heat if
there is demand.
10.5 Frost Protection
Boiler monitors supply and return water temperatures to
enable frost protection which automatically turns boiler and
pump on.
If water in boiler falls below 41°F (5°C), providing boiler is
connected to power, boiler will operate until water temperature
in the system reaches approximately 86°F (30°C).
Frost protection is for boiler only and not for complete Central
Heating System.
10.6 Pump
If electricity is connected to the boiler, regardless if power is

or hot water, boiler pump will operate automatically for one
minute every 24 hours.
10.7 Low Water Pressure Sensor (Internal)
This device protects primary exchanger from damage. It will not
allow boiler to run in a LOW water pressure situation. Low water
condition occurs when water pressure drops below 7.0 psi (0.5
bar).