9.17 Adjusting Maximum Heating Power
Maximum boiler heating power can be reduced to suit

Table showing parameter P13 values according to desired
maximum power model is shown for each single boiler.
To access and edit P13 values, proceed as described in
Section 9.15 Parameter Settings.
Boiler Model - PARAMETER P13 (%)/ Heating Output
Btu/h KW DCB-125 DCC-150
20,400 6.0 0 0
23,800 7.0 4 3
27,200 8.0 7 6
30,700 9.0 11 9
34,100 10.0 15 12
40,900 12.0 22 18
47,700 14.0 30 24
54,500 16.0 37 29
61,400 18.0 44 35
68,200 20.0 52 41
75,100 22.0 59 47
81,900 24.0 67 53
88,700 26.0 74 59
95,500 28.0 80 65
102,300 30.0 88 71
109,200 32.0 96 75
112,600 33.0 100 80
9 - START UP PROCEDURE