SDM630MCT-ML User Manual V1.2
Write demand period: 0~60 minutes, Default 60.
Range: 0~60, 0 means function closed
Length : 4 byte
Data Format : Float
Default 1, min.
Range :1 ~ (Demand Period -1).
Length : 4 byte
Data Format : Float
Write system type:
1 = 1P2W;
2 = 3P3W;
3 = 3P4W,(default);
4 = 1P3W;
Length : 4 byte
Data Format : Float
(KPPA is asked)
Key
Parameter
Programmin
g
Authorizatio
n (KPPA)
Read: to get the status of the KPPA
0 = not authorized;1 = authorized
Write the correct password to get KPPA, enable to
program key parameters.
Length : 4 byte
Data Format : Float
Write the network port parity/stop bits for MODBUS
Protocol, where: 0 = One stop bit and no parity, default.
1 = One stop bit and even parity. 2 = One stop bit and
odd parity.3 = Two stop bits and no parity.
Length : 4 byte
Data Format : Float
Write the Modbus address for the whole meter
In one communication address mode, only one address is
to be set.
Address: 1 to 247 for MODBUS Protocol, default 1.
Length : 4 byte
Data Format : Float
Read: to get the password of the meter
Write: to program the new password of the meter
Default 1000
Length : 4 byte
Data Format : Float
Write the network port baud rate for MODBUS Protocol,
where:
0 = 2400 baud. 1 = 4800 baud.
2 = 9600 baud, default.
3 = 19200 baud. 4 = 38400 baud
Length : 4 byte
Data Format : Float
CT2 = 100mV
Length : 4 byte
Data Format : Float
Default 60, min
Range 0~121,0 means backlit always on ,121 means
backlit always off
Length : 4byte
Data Format : Float
CT1 Range 1-9999A default 100,
Length : 4 byte
Data Format : Float
Note:Access permission is required to set up
CT1 Range 1-9999A,default 100,
Length : 4 byte
Data Format : Float
Note:Access permission is required to set up
CT1 Range 1-9999A,default 100,