80 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are opened because
of the installed internal batteries.
77..33..1111 UUssiinngg tthhee RReemmoottee EEmmeerrggeennccyy PPoowweerr--ooffff SSwwiittcchh
A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this
switch to control the UPS output. The REPO switch de-energizes the critical load and powers down the UPS
immediately, without asking for verification.
The UPS, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You should use
this feature only when you want to de-energize the critical load.
NOTE The following instructions are for the Eaton-supplied REPO switch. If a customer-
supplied REPO switch is used, it may not activate in the same manner; refer to the
operating instructions provided with the switch.
To use the REPO switch:
1. Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see
Figure 45).
The rectifier, inverter, battery, and bypass switchgear open, and the power module is turned off
immediately, without asking for verification.
CAUTION
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases (see Figure 45). To remove the key, rotate the key back to the
vertical position.
3. Restart the UPS by following the procedure in paragraph
7.3.1 Starting the UPS in High-Efficiency Normal Mode (Default Mode) or
7.3.2 Starting the UPS in Bypass Mode.
WARNING
Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are opened because
of the installed internal batteries.