Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04 71
77..22..66 DDiissppllaayy MMeennuu OOppeerraattiioonn
Table 18 describes the menu functions and how to use them.
Table 18. Display Menu Operation
Function Subfunction
Operation
Meters UPS The Meter screens show the UPS meter readings for the unit. The default voltage
displayed on these screens is phase-to-neutral. These can be changed to display
the voltage phase-to-phase (A-B, B-C, C-A). Use the LEFT or RIGHT arrow
pushbuttons to select the METER symbol on the main menu bar, to display the
Meter screens. To scroll through the meter screens, press the UP or DOWN
arrow pushbutton. The current UPS readings are displayed in the information
area of the screen.
Output UPS The Output screen shows output voltage (phase to neutral), output current (each
phase), and frequency being supplied by the UPS, as well as the kVA, kW, and
power factor measurements.
Input UPS The Input screen shows input voltage (phase to neutral), input current (each
phase), and frequency of the incoming utility source, as well as the kVA, kW, and
power factor measurements.
Bypass
The Bypass screen shows the bypass input voltage (phase to neutral), input
current (each phase), and frequency of the incoming utility source, as well as the
kVA, kW, and power factor measurements.
Battery UPS The Battery screen displays the battery voltage (Vdc) and the battery current
(Idc).
Events Use the LEFT or RIGHT arrow pushbuttons to select the EVENTS symbol on the
main menu bar to display the Events screens. A listing of all system events that
are currently active is displayed. The most recent event is listed first. As events
clear, they are removed from the Events listing. To scroll through the events,
press the UP or DOWN arrow pushbutton.
History Use the LEFT or RIGHT arrow pushbuttons to select the HISTORY symbol on
the main menu bar to display the History screen. The history Log lists up to 512
events in chronological order, with the most recent event listed last (once 512 is
reached, the earliest event is overwritten). The end of the log (the most recent
events) is displayed first; scroll upward to view older event listings. To scroll
through the events, press the UP or DOWN arrow pushbutton.
Setup User Function Selection This screen can be used to display user information and show the firmware
versions installed. Use the LEFT or RIGHT arrow pushbuttons to select the
SETUP symbol on the main menu bar to display the Setup screen. Use the UP or
DOWN arrow pushbutton to highlight the function desired, then press the
RETURN pushbutton to display the function screen. See Figure 43 for a typical
screen display.
User Info The User Info screen provides the model, CTO and serial numbers of the UPS, the
Output voltage, frequency, and kVA rating, the input voltage rating, and the
battery run time rating. Use the LEFT or RIGHT arrow pushbuttons to select
USER on the Setup menu bar. Use the UP or DOWN arrow pushbutton. to
select Info, then press the RETURN pushbutton to display the function screen.
To return to the System Setup screen, press the ESC pushbutton.
About The About screen provides the firmware version numbers installed on the UPS.
Use the LEFT or RIGHT arrow pushbuttons to select USER on the Setup menu