86 Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04
1. Select the CONTROLS symbol on the main menu bar on the UPS requiring the charger to be turned off.
The System Control screen is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the CHARGING
RESTING command, then press the
RETURN pushbutton.
77..44..1111 BBaatttteerryy TTeesstt
NOTE 1 This UPS has a user initiated battery test intended to determine if the batteries are able
to support the load.
NOTE 2 The battery test is only able to be initiated when the battery is fully charged. This
normally occurs within 72 hours of the start of a charging cycle. The command will not
be shown if the test is not able to be run.
To start an individual UPS battery test:
1. Select the CONTROLS symbol on the main menu bar on the UPS to be tested. The System Control screen
is displayed.
2. Select Battery on the System Control screen.
3. On the Battery System Control screen, select the RESTING
TESTING command, then press the
RETURN pushbutton.
77..44..1122 UUssiinngg tthhee UUPPSS LLOOAADD OOFFFF CCoommmmaanndd
A UPS Load Off is initiated by the Load Off command on the UPS Control screen. The UPS LOAD OFF controls
the UPSs output by powering down the UPS and de-energizing the critical load.
The UPSs (including Bypass) remains off until restarted.
To use the LOAD OFF command:
1. Select the CONTROLS symbol on the main menu bar on the UPS to be shut down. The System Control
screen is displayed.
2. Select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
LOAD OFF or BYPASS LOAD OFF
command depending on the UPS mode, then press the RETURN pushbutton.
The Verify Action screen is displayed, providing a choice to proceed or abort the shutdown.
CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
4. Select Yes or no, then press the RETURN pushbutton.
Selecting Yes will immediately shut down the UPS and de-energize the critical load. Selecting No will abort
the shutdown.
5. If another UPS is to be shut down, proceed to that UPS and repeat Step 1 through Step 4.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
UPS Operating Instructions