Eaton 93E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164000301—Rev 04 83
14. If not already selected, select UPS on the System Control screen.
15. On the UPS System Control screen, select the LOAD OFF
BYPASS command, then press the RETURN
pushbutton.
The critical load is immediately supplied by the bypass source, in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated.
77..44..33 TTrraannssffeerr ffrroomm NNoorrmmaall ttoo BByyppaassss MMooddee
To transfer the critical load to Bypass mode:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the NORMAL
BYPASS command, then press the RETURN
pushbutton.
All of the UPSs transfer to Bypass mode.
The BYPASS status indicator is illuminated. The power module remains on.
WARNING
Power is present inside the UPS cabinet.
77..44..44 TTrraannssffeerr ffrroomm BByyppaassss ttoo NNoorrmmaall MMooddee
To transfer the critical load to Normal mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the BYPASS
NORMAL command, then press the RETURN
pushbutton.
All of the UPSs transfer to Normal mode. If the power module is not available, the system remains on
bypass and an alarm sounds.
The NORMAL status indicator is illuminated.
77..44..55 TTrraannssffeerr ffrroomm HHEE NNoorrmmaall MMooddee ttoo SSttaannddaarrdd NNoorrmmaall MMooddee
To transfer the load to Standard Normal mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the HE: ENABLE
DISABLE command, then press the
RETURN pushbutton.
All of the UPSs transfer to Standard Normal mode.
The NORMAL status indicator is illuminated.