9. Do the transfer from the bypass mode to the double conversion mode:
a. In the home screen, press Controls.
b. Select UPS controls (Single UPS) or System controls (UPS system).
c. Press Go online button. Confirm your selection.
The UPS is now in the double conversion mode.
Figure 42: Normal positions of the switches
A Bypass input 1 Bypass input switch (BIS)
B Rectifier input 2 Maintenance bypass switch
(MBS)
C UPS output