EasyManua.ls Logo

Eaton 93PM G2 Series - Page 109

Eaton 93PM G2 Series
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9. Do the transfer from the bypass mode to the double conversion mode:
a. In the home screen, press Controls.
b. Select UPS controls (Single UPS) or System controls (UPS system).
c. Press Go online button. Confirm your selection.
The UPS is now in the double conversion mode.
Figure 42: Normal positions of the switches
A Bypass input 1 Bypass input switch (BIS)
B Rectifier input 2 Maintenance bypass switch
(MBS)
C UPS output
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 109
(141)
Eaton 93PM G2 UPS 50 360 kVA User’s and Installation Guide

Table of Contents

Related product manuals