3.5 Software and connectivity features
3.5.1 User interface
MiniSlot Communication Bays there are 4 communication bays for MiniSlot
connectivity cards. MiniSlot cards are quickly installed and hot-pluggable. See
Section 6.1 About communication interfaces for additional information.
3.5.2 Power Management Software
Intelligent Power software products offer tools for monitoring and managing
power devices across the network. See Chapter 6.1 About communication
interfaces for more information.
3.6 Options and accessories
Contact your Eaton sales representative for more information about the available
options and accessories.
3.6.1 Maintenance Bypass Switch
The Maintenance Bypass Switch (MBS) enables power to completely bypass and
isolate the UPS so that the UPS can be safely serviced without interrupting power
to critical systems.
The MBS is available internally as an option for 200 kW/240 kVA frames or in an
external enclosure as an accessory item.
3.6.2 Top air exhaust kit
The top air exhaust kit is used to direct the UPS cooling air front-to-top. The kit
will eliminate the cooling clearance requirement from the back of the unit, and
enable installing the UPS even against a wall, in a corner or back-to-back.
Refer to Section 4.4 Site preparations for further information.
3.6.3 Single feed kit
The Eaton 93PM G2 UPS is configured for dual feed by standard, requiring a
separate feed for rectifier and static bypass input. Single feed kit is available both
as factory installed or on-site installed option.
3.6.4 Field Installed UPM
A Field Installed UPM (F-UPM) can be installed in the cabinet any time in the
future when power needs change. This enables the UPS system to grow with the
business, thus lowering the initial investment required for the system on day one.
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 33 (141)
Eaton 93PM G2 UPS 50 360 kVA User’s and Installation Guide