9.3 UPS environmental specifications
Table 33: UPS environmental specifications
Acoustic noise at 1 m
Rear exhaust
Top exhaust
74 dB(A)
77 dB(A)
Temperature range, operation
Eaton 93PM G2 xxx(200) and 93PM G2
xxx(300) models
+5 °C ... +40 °C
Recommended range * +20 °C ... +25 °C
Temperature range, operation
Eaton 93PM G2 xxx(240) and 93PM G2
xxx(360) models
+5 °C ... +35 °C
Recommended range * +20 °C ... +25 °C
Temperature range, storage and
transportation
-25 °C ... +55 °C
Relative Humidity
Recommended range *
5 % - 95 %
20 % - 60%
Condensation No condensation allowed
Maximum rate of temperature change ** 1.67 °C / 5min
Operating altitude 1000 m without derating
Up to 2000 m with 1% derating per each
additional 100 m above 1000 m
Over voltage category OVC III
Pollution degree PD 2
* ) For maximum lifetime for UPS and batteries, keep the environment in the
recommended range.
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 116
(141)
Eaton 93PM G2 UPS 50 – 360 kVA User’s and Installation Guide