EasyManua.ls Logo

Eaton 93PM G2 Series - UPS Environmental Specifications

Eaton 93PM G2 Series
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ECO Design Directive 2009/125/EC establishing a framework for the setting of
eco-design requirements for energy-related products
Batteries 2006/66/EC on batteries and accumulators and waste
batteries and accumulators
Packaging 94/62/EC on packaging and packaging waste
9.3 UPS environmental specifications
Table 33: UPS environmental specifications
Acoustic noise at 1 m
Rear exhaust
Top exhaust
74 dB(A)
77 dB(A)
Temperature range, operation
Eaton 93PM G2 xxx(200) and 93PM G2
xxx(300) models
+5 °C ... +40 °C
Recommended range * +20 °C ... +25 °C
Temperature range, operation
Eaton 93PM G2 xxx(240) and 93PM G2
xxx(360) models
+5 °C ... +35 °C
Recommended range * +20 °C ... +25 °C
Temperature range, storage and
transportation
-25 °C ... +55 °C
Relative Humidity
Recommended range *
5 % - 95 %
20 % - 60%
Condensation No condensation allowed
Maximum rate of temperature change ** 1.67 °C / 5min
Operating altitude 1000 m without derating
Up to 2000 m with 1% derating per each
additional 100 m above 1000 m
Over voltage category OVC III
Pollution degree PD 2
* ) For maximum lifetime for UPS and batteries, keep the environment in the
recommended range.
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 116