7.2.3 System events
When the UPS system is running in the double conversion mode, it continually
monitors itself and the incoming utility power. In the battery or bypass mode, the
UPS may issue alarms to let you know exactly what event caused the change
from the double conversion mode. System events on the UPS can be indicated
by horns, lights, messages, or all three.
Select Logs in the home screen to look at any currently active events.
System event horn
The system event horn beeps to alert the user that an event requiring
attention is taking place.
System event indicators
The status indicators on the UPS control panel and the event horn let you
know when the UPS system is operating in any mode other than the double
conversion mode. Only the green indicator for normal operation is visible
during normal UPS system operation. The other indicators illuminate to
indicate alarms or events. When an alarm occurs, first examine these
indicators to see what type of event has taken place.
System event messages
When a system event occurs, a message appears in the status bar of the
display. This message is also written to the Active Events log. Some notices
and alarms may be accompanied by an audible horn. To silence the horn,
press any button once.
7.2.4 Menu structure of the 93PM G2 UPS
The following table shows the menu structure of the 93PM G2 UPS.
Table 28: Menu structure of the 93PM G2 UPS
Main menu Submenu Functions
Home - An overview of the UPS operation, including
information on load, efficiency and
consumption.
Meters Meters summary A summary of the UPS or system meters.
Input meters Detailed information on UPS or system input
meters.
Bypass meters Detailed information on UPS or system bypass
meters.
Output meters Detailed information on UPS or system output
meters.
UPM Power