5 UPS system installation
5.1 About UPS system installation
The operator has to supply the wiring to connect the UPS to the local power
source. The installation of the UPS must be made by a locally qualified
electrician. The electrical installation procedure is described in the following
section. The installation inspection and the initial start-up of the UPS and
installing an extra battery cabinet must be carried out by an authorized Eaton
Customer Service Engineer or by other qualified service personnel authorized by
Eaton.
CAUTION
To avoid physical injury or death, or damage to the UPS or the load
equipment, follow these instructions during the UPS system installation.
CAUTION
In case of condensed moisture inside the UPS cabinet, dry the cabinet
with a blower before starting up the system.
5.2 Steps to install the UPS
Power wiring can be routed through the bottom or top of the cabinet. Control
wiring can be routed through the rear, bottom, or top of the cabinet, with
connections made to easily accessible terminals. See Figures 13: Removing the
right panel and 14: Gland plate locations.
The interface wiring may be wired from top of the unit using cable glands in the
plate on top of the unit. Wires can be routed through the communication cable
conduit.
1. Remove the right panel by loosening the screws.
2. For installing the power cables and DC source signal wires, remove the
screws of the top, bottom, or rear cable access gland plate.
3. For installing the control wiring, route the wires through the communication
cable access gland plate. See Figure 14: Gland plate locations.
4. Depending on the installation method, use the appropriate plate.
5. Route all the cables through wire way to the UPS terminal blocks.
6. Reinstall wire entry plate and install conduit if needed.
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 57 (141)
Eaton 93PM G2 UPS 50 360 kVA User’s and Installation Guide