3. Press Continue to return to the previous screen.
You have 3 attempts to type in the password. If an incorrect password is given
more than 3 times, you need to wait for 30 minutes before trying again.
Table 31: Default passwords
Level Name Password Description
1
USER NONE USER
2
CONTROL 1111 USER + CONTROL
3
CONFIGURATION 0101 USER + CONTROL +
CONFIGURATION
4
SERVICE Service Only USER + CONTROL +
CONFIGURATION +
SERVICE
To modify the user settings, you need to enter the level 2 password.
7.4 System control instructions
7.4.1 Start the UPS system in the double conversion mode
The UPS system can consist of a single UPS or several parallel UPSs. UPSs
with their MOB open are not considered as part of the system.
To start the UPS system.
1. Close the UPS input feeder circuit breaker.
2. Close the UPS bypass input feeder circuit breaker.
3. Wait for the UPS control panel display to become active and to indicate logic
power.
4. Repeat steps 1-3 for each individual UPS in the system.
5. In the home screen, press Controls.
The System controls screen appears.
6. In the System controls screen, make sure that the system status is
SHUTDOWN.
7. In the System controls screen, press the Go online button.
If Auto Bypass is enabled (factory default), the critical load is immediately
supplied by the bypass source, in the bypass mode, until the inverter turns
on and the UPS transfers to the double conversion mode. The status
indicator on the UPS control panel indicates that the UPS is in the bypass
mode. If auto bypass is not enabled, the UPS output remains off until the
UPS system transfers to double conversion mode.