EasyManua.ls Logo

Eaton 93PM G2 Series - Page 36

Eaton 93PM G2 Series
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frame Power
rating
Static switch
rating
# of power
modules
Power
module
rating
Output
power
factor
360 kVa 60-360 kVa 360 kVa 1-6
The UPS frames can be connected in parallel to create even larger systems. A
maximum of four UPSs can be connected in parallel.
UPS options and accessories
The following table shows different standard and optional UPS features.
Table 3: Standard and optional UPS features
Feature Frame
200/240 kVA frame 300/360 kVA frame
Touch screen display X X
Battery start X X
Integrated backfeed protection X X
Static bypass protective fuses X X
Internal maintenance bypass switch
(MBS)
O
Battery breaker for external
batteries
O O
Sync control interface O O
Top air exhaust kit O O
Parallel cable kit O O
Single feed kit O O
X= Standard
O = Optional
= Not available
Additional options and accessories are also available. These include different
software and connectivity options and external switchgear and power distribution
options.
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 36 (141)
Eaton 93PM G2 UPS 50 360 kVA User’s and Installation Guide