Table 8: Recommended multi-core cable and fuse sizes for rectifier input, bypass
input and UPS output connections
UPS model
Phase cables [mm
2
]
Rectifier,
bypass and
mainte-
nance
bypass
input fuse
[A] PE cable [mm
2
]
93PM G2 50
(200)
35 100 16
93PM G2 100
(200)
95 200 50
93PM G2 150
(200)
185 315 95
93PM G2 200
(200)
240 400 120
93PM G2 240
(240)
2 x 120 500 120
93PM G2 50
(300)
35 100 16
93PM G2 100
(300)
95 200 50
93PM G2 150
(300)
185 315 95
93PM G2 200
(300)
240 400 120
93PM G2 250
(300)
2 x 120 500 120
93PM G2 300
(300)
2 x 185 630 185
93PM G2 360
(360)
2 x 185 700 240
© Eaton Corporation plc 2020. All rights reserved. Revision: 001 Document ID: P-164000956 45 (141)