42 Eaton 9PX Lithium-Ion P-164001006—Rev 01
Table 9. Weights and Dimensions (Continued)
Model
Dimensions D x W x H(inch/mm) Weight (lb / kg)
9PXEBM48RT-L 17.6 x 17.2 x 1.7 / 448 x 438 x 42.9 36.5 / 16.6
9PXEBM72RT-L 23.7 x 17.2 x 1.7 / 603 x 438 x 42.9 46.6 / 21.2
Table 10. Electrical Input
Model Default Input
(Voltage/Max Current)
Input Nominal Voltages Input Voltage Window at
Rated Load
9PX1500RT-L 120V / 12.5A 100V, 110V, 120V, 125V 100–138V
9PX2000RT-L 120V / 16A
9PX3000RT-L 120V / 24A
9PX1500GRT-L 208V / 7.2A 200V, 208V, 220V, 230V, 240V 176V-276V
9PX2200GRT-L 208V / 10.57A
9PX3000GRT-L 208V / 14.42A
Nominal Frequency 50/60Hz auto-sensing
Frequency Range 40-70Hz before transfer to battery
Bypass Voltage Range
-20% / +15% of nominal value (default)
Noise Filtering Input EMC filter
Table 11. Electrical Input Connections
Model Input Connection Input cable
9PX1500RT-L 5–15P 8ft / 2.4m
9PX2000RT-L 5–20P 8ft / 2.4m
9PX3000RT-L L5–30P 8ft / 2.4m
9PX1500GRT-L IEC-C14, IEC 10A 6ft / 1.8m
9PX2200GRT-L
IEC-C20, 16 A inlet
L6-20P to C19 jumper provided
6ft / 1.8m
9PX3000GRT-L
Table 12. Electrical Output
All Models Normal Mode Efficiency Mode Battery Mode
Voltage Regulation ±1% ±2%
Efficiency
90.0% for 1.5K LV models
91% for 1.5K G models
91.4% for 2K LV models
93% for 2K G models
94% for 3K G models
95.8% for 1K5 LV models
96.5% for 1.5K G models
96.8% for 2K LV models
98% for 2K G models
97.2% for 3K LV models
98% for 3K G models
84% for 1.5K LV models
87.5% for 1.5K G models
86% for 2K LV models
90% fo r 2K G models
86% for 3K LV models
89% for 3K G models
Model Specifications