44 Eaton 9PX Lithium-Ion P-164001006—Rev 01
Table 13. Electrical Output Connections (Continued)
Model Output Connection Output Cable
9PX2200GRT-L
(4) IEC10A + (1) IEC16A
(2) IEC10A + (1) IEC16A group 1
(2) IEC10A group 2
(2) IEC 10A
9PX3000GRT-L
Table 14. Environmental and Safety
Certifications
IEC/EN 62040-1
IEC/EN 62040-2 : Cat. C1
IEC/EN 62040-3
UL1778 5th edition
CSA 22.2
EMC ( Emissions)*
CISPR22 Class B
FCC part 15 Class B / ICES-003
EMC (Immunity)*
IEC 61000-4-2, (ESD): 8 kV Contact Discharge / 15 kV Air
Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): Power (Coupling network) 4 kV / Ethernet
(Coupling
clamp) 2 kV
IEC 61000-4-5, (Surges): 2 kV Differentiel Mode / 4 kV Common
Mode /
1 kV Ethernet
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
* for output cable < 10m.
Agency Markings* CE / cULus / NOM / Energy Star / BSMI
Operating Temperatures
0 to 40°C (32 to 104°F) in Online mode, with linear derating for
altitude
Note: thermal protection switches load to Bypass in case of
overheating.
Storage Temperatures
0 to 40°C (32 to 104°F) with batteries
-25 to 55°C (-13 to 130°F) without batteries
Transit Temperature
-25 to 55°C (-13 to 130°F)
Relative Humidity 0 to 96% no condensing
Operating Altitude Up to 3,000 meters (9,843 ft) above sea level, no derating for
35°c (95°F) room temperature
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
Audible Noise
< 47 dBA at 1 meter typical for 2K et 3K models
< 40 dBA at 1 meter typical for 70, 1K et 1K5 models
* 9PX1500RT-L, 9PX2000RT-L, 9PX3000RT-L, 9PX1500GRT-L, 9PX2200GRT-L, 9PX3000GRT-L have CE/ cULus/Energy Star/ BSMI.
9PXEBM48RT-L, 9PXEBM72RT-L have CE / cULus / NOM.
Model Specifications