46 4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09
NOTE 1 The external battery cabinets are the same dimensions as the UPS cabinets. Refer to
the 2.1 Preparing for Installation section for unpacking and cabinet setup.
NOTE 2 If you are installing multiple EBM(s) upstream to the UPS, repeat the setup as described
in this section.
1. Open the carton containing the external battery cabinet cable assembly and position it in the desired
location next to the UPS.
2. If you are rack-mounting the EBM cabinet, refer to the UPS rack-mount installation procedure (see
2.6 Rack-Mount Installation ). If not, proceed to the next step.
3. Install the anchor brackets to the floor if applicable (see 2.5 Anchor Bracket Installation ).
CAUTION
Make sure all AC power is removed from the UPS. Observe all electrical safety precautions.
4. Push in the EBM DC emergency disconnect switch on the rear EBM panel and turn the switch lockout key
(see Figure 37 ).
NOTE The UPS and EBM AC/DC terminal covers are shipped in the UPS and EBM accessory
kit and do not come installed on the UPS or EBM chassis.
Figure 38. UPS to Standard Battery Cabinet Connection Locations
EBM Terminal
Covers
UPS DC
Terminal
Cover
DC Emergency
Disconnect
Switch
EBM UPS
1. Route the EBM DC input/output cables to the terminal blocks as shown in (Figure 39).
Standard Battery Cabinet Installation