Eaton 9PXM - Figure 65. In;Out Settings Menu

Eaton 9PXM
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 09 83
In/Out Settings
The In/Out Settings menus allows control of input and output limits.
Figure 65. In/Out Settings Menu
Local Settings
In/Out settings
On/Off settings
Battery settings
Input signals
Comm settings
User password enable
User password settings
Settings
Output voltage
High Efficiency mode
Protected Bypass
Overload prealarm
Redundancy
Byp freq limit
Byp volt min limit
Byp volt max limit
In/out settings
Output voltage
110 V
120 V
127 V
High Efficiency mode
Disabled
Enabled
Protected Bypass
Enabled
Disabled
Overload prealarm
100
Byp freq limit
Byp volt min limit
Byp volt max limit
Redundancy
Level 0
Level 1
Level 2
%
Level 3
Level 4
4
Hz
12
%
12
%
[110V] [120V][127V]
Default:[120V][127V]
[Enabled] [Disabled]
Power the output from
Default: Disabled
[Enabled] [Disabled]
Default: Enabled
[10%] … [102%]
Load % when overload
alarm occurs
Default: 100%
Set redunancy level
Default: 0
Default disables
transfer to Bypass if the
measured bypass
frequency is below
the nominal 4%
Default disables
transfer to Bypass if the
measured bypass voltage
level is below the nominal
output voltage minus 12%
Default disables
transfer to Bypass if the
measured bypass voltage
level is above the nominal
output voltage plus 12%