28 INSTALLATION AND OPERATION MANUAL 25-16330-B December 2019 www.eaton.com
Technical Specification
It is current limited to 30mA using a resettable polyswitch. Class change and test
conditions do not operate this output. If operated under a fire alarm condition, the
FRE LED will illuminate and will remain illuminated until the fire alarm is reset.
Ensure the polarity of the connections are observed at all times and end of line
resistors (6K8 5%) are fitted to ensure correct operation.
Output to Fire Alarm Protecting Equipment
(Option 7.10 EN54 Part 2 Option A)
This output, which is fused, and monitored using a 6K8 end of line resistor, is used
for the transmission of the fire signals to controls for automatic fire protecting
equipment (e.g. Door released units etc). It operates by providing a 24V DC output to
an auxiliary device (e.g. relay).
It is current limited to 30mA using a resettable polyswitch. Class change and test
conditions do not operate this output. If operated under a fire alarm condition, this
output remains energised until the fire alarm is reset.
Ensure the polarity of the connections is observed at all times and end of line
resistors (6K8 5%) are fitted to ensure correct operation.
Output to Fault Warning Routing Equipment
(Option 8.9 EN54 Part 2)
This output, which is fused and monitored using a 6K8 end of line resistor, is used
for the transmission of fault signals to fault warning routing equipment. This output
is monitored using a 6K8 end of line resistor and is current limited to 30mA. Under
normal condition it operates by providing 12V DC which can be connected directly to
a 12V auxiliary device (it is current limited to 30mA).
Under fault conditions or even if the panel is powered down, this output will be
switched to 0V.
Ensure the polarity of the connections is observed at all times and end of line
resistors (6K8 5%) are fitted to ensure correct operation.
Delays to outputs (Option 7.11 EN54 Part 2)
The panel has the option to delay the operation of panel sounders, the Fire Routing
equipment output and the Fire Protecting equipment. This delay is selectable using
the Site Installer download software. The delay is configurable in increments of 1
minute up to a maximum of 10 minutes.
This delay can be enabled and disabled at access level 2.
The has the facility for a specific call point to override this delay by programming this
call point via an input interface to provide an evacuate signal using the
Site Installer software.