32 INSTALLATION AND OPERATION MANUAL 25-16330-B December 2019 www.eaton.com
Installation
Fixing Details
Read all the installation instructions before commencing with the installation.
The installation of this panel must be carried out by a suitably
qualified /trained person.
The installation must comply with IEE wiring regulations and with
BS5839 part 1 and part 6.
The electronic components within the fire panel are Static Sensitive.
Do not touch the electronics directly.
Mounting the Backbox
The panel can be flush mount or surface mounted.
1. For Surface Mount; drill four holes and fix the backbox to the wall.
2. For Flush Mount the backbox requires a hole 310mm x 355mm with a depth
of 117mm.
Figure 2. Back Box dimensions
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables
and fit the glands.