97INSTALLATION AND OPERATION MANUAL 25-16330-B December 2019 www.eaton.com
Appendix
Micro Input Module Wiring
To install the device
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram.
3. Recommended Cable Type: FIRETUF, FP200, MICC.
ote: N No addressing of the interface is required. See control panel operation for
details. There are no serviceable parts so no maintenance procedures apply.
Figure 64. Standard connections
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor provided must always be fitted, even if the
input is unused.
3. Monitored inputs can detect open or short circuit faults.
Battery Disposal Instructions
Although batteries contain lead and small amounts of antimony and arsenic, they are
safe if handled according to the accompanying guide. The battery cells must not be
dismantled as this involves several hazards, which are best handled under controlled
conditions, using specialised equipment. No attempt should be made to repair any
batteries; they should be treated as disposable when they have outlived their use.
Batteries must be disposed of in accordance with current waste disposal and
pollution legislation and in particular; The Environment Protection Act 1990, Special
Waste Regulation 1996. It is recommended that the following authorities are
contacted before any attempt is made to dispose of batteries; Environment Agency
Local office, Local Authority Environmental Health or Waste Handling department.