System Overview
Technical Specication
Power Supply (Approved EN54 pt 4)
Mains
Nominal Voltage 230V AC + 10%, -15%
Nominal Current 40mA
Maximum Current 500mA
Input Fuse R1 Anti Surge 1.6A
Output Voltage including tolerances 26V = 25 to 28.6V
26V RAW = 20.4 to 29.0V
5V Output = 4.85V to 5.15V
Ripple Voltages 26V = 800mV
26V RAW = 800mV
5V Output = 430mV
Maximum Loadings 26V O/P = 0.48A *I max b
26V RAW O/P = 1.2A *I max b
5V = 0.5A
Standby Current
(2 Loops Loaded)
26V = 140mA *I max a
26V RAW = 50mA *I max a
26V = 140mA *I min
26V RAW = 50mA *I min
5V = 80mA
* I max a, I max b & I min = Current as specified in BS EN54-4 Published 2006 (Amendments 1 & 2)
Please refer to local standards for details of the maximum allowable area to be
covered by a single spur.
Integral Power Supply and Battery
The panel is designed for ease of installation, the power supply and battery are
integral to the main control panel so only a single panel is required.