24 INSTALLATION AND OPERATION MANUAL 25-16330-B December 2019 www.eaton.com
Technical Specification
Batteries
Number of Batteries 2
Manufacturer YUASA NP7-12
Capacity 7Ah
Battery Fuse 6.3A Anti-Surge (F4)
Maximum battery current 3.0A
Standby current (mA) 125 (2 loops)
Maximum Charging Current to the
Batteries
0.65A
Float Voltage 27.4V
Final Voltage 21.0V
Charging Characteristics Constant Voltage with 0.65A limit with temperature compensation
Maximum current drawn from the
batteries when the mains is not available
3.0A
Deep Discharge Protection 20.6V
Battery Internal Impedance Fault >0.5Ω
Inputs
Addressable Loops
Max Number 2
Max Loop Load per loop 200mA
Max Number of Addressable Devices
per loop
200
Class Change Operated by external volt free contact
Max Cable Length 2km
Min Recommended cable size (csa) 1.5mm
2
Zones
Max Number 250
Max Per Loop 200
Max LED Indicated 32