25INSTALLATION AND OPERATION MANUAL 25-16330-B December 2019 www.eaton.com
Technical Specification
Outputs
Conventional sounder circuits
Nominal Voltage 20.4V - 29.0V
Number of sounder circuits 4
Total Sounder Load 1.0A (FH1204)
Maximum Sounder Circuit Load 800mA
Sounder Circuit Fuses (F1/2/3/4) 1.6A (Quick Blow)
End of line resistor 6k8
Fire Routing Equipment
Nominal Voltage 20.4V - 29.0V
Max Load 60mA
Fused (PTC2) 100mA polyswitch
End of Line resistor 6k8
Max Cable Length 2km
Min Recommended cable size (csa) 1mm
2
Fire Protecting Equipment
Nominal Voltage 20.4V - 29.0V
Max Load 60mA
Fused (PTC4) 100mA polyswitch
End of Line resistor 6k8
Max Cable Length 2km
Min Recommended cable size (csa) 1mm
2
Fault Routing equipment
Input Voltage 30V
Input Current 30mA
Fused (PTC1) 100mA polyswitch
End of Line resistor 6k8
Max Cable Length 2km
Min Recommended cable size (csa) 1mm
2
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load 24V, 1A
Fuse (PTC5) 1.1A polyswitch
Max Cable Length 1km
Min Recommended cable size (csa) 2.5mm
2

Table of Contents